General features:
Power Supply: 24 .. 240 VAC/ DC
Output speed can be set 5 variations
Ambient temperature: -20 .. +40/ +50 °C
Compact Al body, by IP66 ingress protection
Inside Heater to prevent condensation
Manual Override option
Accessories like mounting kits, terminal compartments, separately installed contacts for positioning etc.
Types and Zone enclosures:
ExRun.. EP-, Flameable danger zones, by Zone 1,2,21,22 (for gases and dusts)
RedRun.. EP-, Flameable danger zones, by Zone 2, 22 (for gases and dusts)
InRun.. Types that suitable for non-dangerous zone applications
Constructional design:
Body of actuator + (ExRun-..; RedRun-...; InRun-...) + adapter set (mounting legs and coupling for connection of valve and actuator stem)
Output thrust ranges and accepted valve travel:
ExRun..; RedRun...; InRun - xy - where "xy" is the available thrust load in Newton (e.g.: 2 500/ 5000 N)
Sizes at all types:
Examples:
ExRun - 25.50-Y (2 500 - 5 000 N)
RedRun - 5.10 (500 - 1000 N); etc..
Sizes and mounting schemes can be studied in manufacturer brochures/ drafts for all types
Protection types:
ATEX Zone 1, 2, 21, 22 for gases, vapours and mists - ATEX, IECEx, EAC, UL, CSA Certification categories
ATEX Zóna 21, 22 flamable dusts - TEX, IECEx, EAC, UL, CSA certifications
Non dangerous zones by IP66 protection class
Control&feedback/ types and abbreviations:
For types ExMax...; ExRun...; InRun... :
Control:
Open & Close, or 3-point control; example: ExRun - 5.10
0 .. 10 VDC, 4. . 20 mA; e.g. ExRun - 5.10 -Y (control and feedback by 0..10 VDC/ 4..20 mA), vagy ExRun-5.10-U (control: open&close/3 point; feedback by:0..10 VDC/ 4..20 mA)
Feedback:
No feedback; examle: ExRun-25.50, RedRun-5.10; InRun-75.100
Feedback by 0 .. 10 VDC or 4 .. 20 mA , example: ExRun-25.50-Y/ U; RedRun-75.100-Y/ U; etc.
Further technical features:
Actuator travel: 5 .. 60 mm
Output speed: 2..15 mm/sec
Terminal compartment/ box connection design
Variable output speeds by 5 choices
Ambient temperature: -20 .. + 40 °C (T6), or -20 .. +50 °C (T5)
Basic information for valve adaptation:
Manufacturer of Valve
Type (duty) of valve
Sizes DN - or individually designed solutions where well detailed drawings by noting dimensions and geometry and adding used raw material are needed
Accessories:
EP (Ex) types, or IP66 protection types, positioners as external equipment, contacts and special mounting kits
Manual override solutions